HUECK Trigon 50 FP30

-Elevation widths 50 mm
-Maximum pane size 1500 mm x 3000 mm
-Fire protection façade EI30
-Fixing spacings ≤ 6000mm

Construction

  • Thermally insulated aluminium façade design in mullion-transom construction for vertical façade walls (mounting position tilted by up to 10° from the vertical)
  • Mullion, transom and cover profiles from the Hueck Trigon modular façade system; slide-in supplementary profile including non-combustible insulating strips. Insulating zone formed by an insulating layer strip and glass fibre-reinforced polypropylene as a spacer profile
  • Same geometry for mullion and transom

Elevation width

  • Transom and cover profiles with an elevation width of 50 mm in various profile geometries

Field of application

  • The permitted height of fixing points for the glazed storeys is ≤ 6000 mm in the case of mullion profiles
  • The width and height of the façade construction is unlimited
  • The max. mullion spacings are ≤ 3024 mm

Panels

  • The panels are to be manufactured from “PROMATECT-H” or “Promaxon Type A” fire-resistant boards with a thickness of at least 18 mm, optionally clad with 2 mm aluminium or steel plate. Alternatively, instead of metal cladding, it is possible to mount ESG or VSG glazing with a thickness of at least 6 mm on both sides.
  • Max. permissible panel size of 1250 x 2500 mm or 1500 x 3000 mm depending on panel variety, in a choice of vertical or horizontal format

Glazing

  • Contraflam single glazing Securit, Securit Decorglass, Stadip, Stadip Protect Thickness: ≥ 16 mm
  • Contraflam insulating glazing Climalit, Climaplus, Climatop, ScreenLine Thickness: ≥ 26 mm
  • Max. permissible glass size for EI30 (F30): 1500 x 3000 mm, in a choice of vertical or horizontal format

Gaskets

  • Shaped gasket pieces covering the entire joint area are used at the transom connection
  • Optional single-piece or two-piece EPDM gaskets as external gasket
  • Can be inserted on site without sealing material

Highlights

  • Water tightness: Static class RE 750 according to DIN EN 12154, dynamic class 250 / 750 Pa according to DIN EN 13050
  • Air permeability: Class A4 according to DIN EN 12 152
  • Resistance to wind load: Test load 2000 Pa / safe load 3000 Pa according to DIN EN 13116
    Permissible load: 2.4 kN/m²; increased load: 3.6 kN/m²

Connection/transition

  • Connections to glass façades with no fire protection classification are permissible if the local building authority consents to this. The width of the required safety area is defined by the building authority (usually 1 m).

Sun protection

  • If the façade construction is installed in conjunction with a sunshade, the latter must be made of building materials of at least standard flammability (building material class B2 according to DIN 4102 or E according to EN 13501-1). Evidence must be provided of the structural strength of the sunshade's mounting.